NEW QUESTION 29
During the troubleshooting phase, what is the first step?
- A. Isolate
- B. Repair
- C. Verify
- D. Test
Answer: C
NEW QUESTION 30
What is the maximum allowable horizontal cable length?
- A. 30 m (100')
- B. 90 m (295')
- C. 10 m (33 ')
- D. 50 m (164')
Answer: B
NEW QUESTION 31
Which of the following is permissible if the available firestop assembly is NOT capable of properly restoring the necessary fire rating?
- A. Add more of the product to increase the rating
- B. Move the installation to another location
- C. Obtain written assistance from the manufacturer
- D. Substitute products from another assembly
Answer: C
NEW QUESTION 32
Which of the following types of construction protects the optical fiber by supporting each strand of glass with a buffer coating extruded over the base optical fiber's 250 um acrylate coating?
- A. Tight buffered
- B. Loose tube
- C. Ribbon
- D. Single stranded
Answer: A
NEW QUESTION 33
What is the characteristic impedance of Series-6 coaxial cable?
- A. 75 ohms
- B. 100 ohms
- C. 50 ohms
- D. 25 ohms
Answer: A
NEW QUESTION 34
What is the minimum number of consolidation points that should serve an open office furniture cluster?
- A. 0
- B. 1
- C. 2
- D. 3
Answer: A
NEW QUESTION 35
How much cable slack should be left in the work area after termination?
- A. 3m (10')
- B. 1m (3.3')
- C. 1.2 m (4')
- D. 0.5m (1.6')
Answer: B
NEW QUESTION 36
Which type of tester includes a set of modular plugs?
- A. Cable-end locator kit
- B. Multimeter
- C. Inductive amplifier
- D. Tone generator
Answer: A
NEW QUESTION 37
What is the most appropriate administration class for an infrastructure with multiple telecommunications spaces within one building?
- A. Class 4
- B. Class 2
- C. Class 1
- D. Class 3
Answer: B
NEW QUESTION 38
Which of the following is a floor serving space that serves as a point of termination for horizontal and backbone cables?
- A. TE
- B. EF
- C. ER
- D. TR
Answer: D
NEW QUESTION 39
A third 90-degree bend may be permitted in a conduit run if one of the bends is located within ____ of the cable feed end?
- A. 450 mm (18")
- B. 300 mm (12")
- C. 483mm (19")
- D. 375 mm (15")
Answer: B
NEW QUESTION 40
Which of the following topologies is the recommended topology for distribution systems in campus environments?
- A. Tree
- B. Ring
- C. Hierarchical Star
- D. Star
Answer: C
NEW QUESTION 41
What grade of plywood is recommended for use with ICT systems?
- A. A/D
- B. B/C
- C. C/D
- D. A/C
Answer: D
NEW QUESTION 42
Which of the following is a benefit of air-blown optical fiber cable?
- A. It requires less testing than other types of cables
- B. It is significantly cheaper than other types of cables
- C. It can be recovered and reused
Answer: C
NEW QUESTION 43
What is the size of a rack-mounted unit (RMU)?
- A. 45 mm (1.75")
- B. 25 mm (1")
- C. 38 mm (1.5")
- D. 50 mm (2")
Answer: A
NEW QUESTION 44
The information transmitted by an ICT system can originate in two fundamental forms:
- A. Light and sound
- B. Analog and digital
- C. Synchronous and asynchronous
- D. Progressive and regressive
Answer: B
NEW QUESTION 45
You are terminating a category 3 cable. What is the maximum permissible amount of untwisting?
- A. 25 mm (1")
- B. 100 mm (4")
- C. 75 mm (3")
- D. 38 mm (1.5")
Answer: C
NEW QUESTION 46
......